1360A

Fieldbus, 1 Pr #16 Str TC, PP Ins, OS, PVC Jkt, PLTC-ER, ITC-ER, c(UL)CMG

...
Fieldbus, 1 Pair 16AWG (7x24H) Tinned Copper, PP Insulation, Overall Beldfoil® Shield, Orange PVC Outer Jacket, PLTC-ER, ITC-ER, c(UL) CMG
Request Sample Get Product Alerts

Specifications
Product Overview

Suitable Applications

harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details
Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 16 AWG 7x24 TC - Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) PP - Polypropylene 0.029 in (0.74 mm) 0.117 in (2.97 mm) Blue & Orange
Outer Shield
Shield Type Material Coverage Drainwire Type Notes
Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7x28) TC Foil In - with polyester wrap
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC - Polyvinyl Chloride 0.065 in (1.7 mm) 0.40 in (10 mm) Yes

Overall Cable Diameter (Nominal)

0.40 in (10 mm)

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Max. Capacitance Unbalance Nom. Capacitance Cond-to-Shield Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 5.9 Ohm/1000ft 1.2 pF/ft (3.9 pF/m) 45 pF/ft 100 Ohm 66% 8 Amps per Conductor at 25ºC

Nom. Outer Shield DCR

7.5 Ohm/1000ft (25 Ohm/km)

High Frequency (Nominal/Typical)
Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 0.039 0.08 dB/100ft
High Frequency
Frequency [MHz] Max. Insertion Loss (Attenuation) Max./Min. Input Impedance (unFitted) [Ohm]
0.031 0.091 dB/100ft 100
Voltage
UL Voltage Rating
300 V (CMG, PLTC-ER), 150 V (ITC-ER)
Mechanical Characteristics
Temperature
UL Temperature Operating
105°C -40°C to +105°C
Bend Radius
Stationary Min. Installation Min.
4 in (100 mm) 4 in (100 mm)

Max. Pull Tension

84 lbs (38 kg)

Bulk Cable Weight

69 lbs/1000ft

Standards and Compliance

Environmental Suitability

Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial

Flammability / Reaction to Fire

UL 1685 UL Loading, FT4, IEEE 1202, IEC 60332-1-2

CPR Compliance

CPR Euroclass: Eca

NEC / UL Compliance

Article 725, Article 727, Article 800, CM

CEC / C(UL) Compliance

CMG

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

UK Regulation Compliance

UKCA Mark

APAC Compliance

China RoHS II (GB/T 26572-2011)

Product Notes

Notes

Fieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket.

History

Update and Revision

Revision Number: 0.509 Revision Date: 12-22-2023

Part Numbers
Item # Color Putup Type Length UPC Footnote
1360A 0031000 Orange Reel 1,000 ft 612825112631 C

Resources